Description
The JC08W-mA Series split-core current transformer is compact and lightweight. It has a 2500:1 or 3000:1 ratio, providing either 25A/10mA or 30A/10mA, depending on the model.
The JC08W-mA Series split-core current transformer has a current range of 0.01~42A or 0.01~45A, depending on the model, and can withstand up to 70A continuously. Linearity is up to 0.5%, after taking into account the offset. The phase angle error is +1+/-1 degree.
The JC08W-mA CT has an opening of 8.5mm, and is often used in energy metering, power quality monitoring, HVAC & pumps and distributed measurement systems. The low mA output allows for longer lead lengths without losing accuracy.
Notice
• Core contact surface is waterproofed; however if it gets rusty, you can reuse after removing rust by spraying WD-40 or CRC5-56 on the rusted surface(s).
• Do not use any other chemicals except WD-40 or CRC5-56 on housing or any parts.
• CTs can be delivered with a customized-length output lead cable.
• Silicone rubber reducing sleeves for central positioning of thinner conductors (5.5mm~6.5mm) are optional available.